MQ Controller
The MQ Controller provides communication and control between the field devices and the other nodes on the control network. Control strategies and system configurations created on earlier DeltaV™ systems can be used with this powerful controller. The MQ Controller provides all the features and functions of the MD Plus Controller, with the same amount of memory.
分类:
Emerson
关键词:

咨询热线:
产品描述
Introduction

Advanced operations. The MQ controller provides the DeltaV platform to migrate PROVOX and RS3 controllers, and also supports the PROVOX and RS3 Migration I/O interfaces.
The existing PROVOX I/O remains in place using the migration I/O interface to PROVOX with support of up to 750 real I/O signals. Serial datasets are migrated to DeltaV serial cards and all virtual I/O are no longer required due to the direct module references possible in the DeltaV system.
RS3 system migrations to the DeltaV system are fully supported with MQ Controllers and the migration I/O interface for RS3.

Power, Mounting, and Memory |
|
Power Requirement |
Supplied by System Power Supply through 2-wide Power/ Controller Carrier |
Fuse Protection |
3.0 A, non-replaceable fuses |
Power Dissipation |
5.0 W typical, 7.0 W maximum |
Mounting |
On right slot of power/controller carrier |
User Memory |
48 MB |
Primary Control Network |
8-pin RJ-45 connector |
Redundant Control Network |
8-pin RJ-45 connector |
LED Indicators (ON Status) |
|
Green – Power |
Indicates DC power is applied |
Red – Error |
Indicates an error condition |
Green – Active |
Indicates that the controller is operating as the primary controller |
Green – Standby |
Indicates that the controller is operating as a backup controller (reserved for future use) |
Yellow Flashing – Pri. CN |
Indicates valid primary control network communication |
Yellow Flashing – Sec. CN |
Indicates valid secondary control network communication |
All except Power flashing |
Visual identification of controller initiated from user interface software by ping command |
All except Power flashing, alternating even and odd |
Firmware upgrade in progress |
Environmental |
|
Operating Temperature* |
-40° to 70°C (-40° to 158°F) |
Storage Temperature |
-40° to 85°C (-40° to 185°F) |
Relative Humidity |
5 to 95%, non-condensing |
Airborne Contaminants |
ISA-S71.04-1985 Airborne Contaminants Class G3 Conformal coating |
Shock (normal operating conditions) |
10 g ½-sine wave for 11 ms |
Vibration (operative limit) |
1 mm peak-to-peak from 5 Hz to 16 Hz, 0.5 g from 16 Hz to 150 Hz |
*Operating any electronics at the higher end of its temperature range for long periods of time will shorten its expected lifetime, see Effects of Heat and Airflow Inside an Enclosure White Paper for more information.
Certifications
The following certifications are available on the MQ controller (see actual certificates for exact certifications).
• CE
EMC- EN 61326-1
• FM
FM 3600
FM 3611
• CSA
CSA C22.2 No. 213
CSA C22.2 No. 61010-1
• ATEX
EN 60079-0
EN 60079-7
• IEC Ex IEC60079-0 IEC60079-7
• Marine Certifications: IACS E10
ABS Certificate of Design Assessment DNV Type Approval Certificate
• Wurldtech
Achilles Communications Certification Level 2
Hazardous Area/Location
The MQ Controller can be installed and used based on the following Standards (see actual certificates for exact product markings):
• FM (USA)
Installation:
Class I, Division 2, Groups A, B, C, D, T4
• cFM (Canada)
Installation:
Class I, Division 2, Groups A, B, C, D, T4
• ATEX
II 3G Ex ec IIC T4 Gc
• IEC Ex
Installation:
II 3G Ex ec IIC T4 Gc
Regarding the Installation instructions please refer to the following Documents: Class 1 Division 2 Installation Instructions DeltaV M-series (12P1293)
Zone 2 Installation Instructions DeltaV M-series (12P2046)
产品留言